Skip to content Skip to footer

EP2000 Pro Series (DC:24V 600-1000W)

Low Frequency Power Inverter/Charger 600W~1000W | 24V | 10~15A

EP2000 PRO series inverter is a cost effective, intelligent with UPS function. The comprehensive LCD offers user-configurable and easy-accessible button adjustment such as battery charge current, battery charge voltage, frequency, buzzer etc. It’s perfect for the user who need a simple and economical inverter,with user-friendly installnation and setting.Tower and rack design available for different choices.

Model Certification & Standards
EP20-0624 PRO/0824 PRO/1024 PRO CE-LVD(EN IEC62109-1:2010, EN IEC62109-2:2011)
EP20-1024PRO/0624PRO/0824PRO CE-EMC+LVD(EN6100-6-4:2007, EN6100-6-2:2005+EN IEC62109-1:2010, EN IEC62109-2:2011)
EP20-1024PRO/0624PRO/0824PRO IEC60950-1:2005A+1:2009+A2:2013
EP20-0624 PRO/0824 PRO/1024 PRO EN IEC62040-1:2019
Category: Tag: Product ID: 26225

Description

■ Pure sine wave output

■ Smart LCD setting ( frequency , charge voltage,charge current, etc).

■ 3 steps charging algorithm

■ Built in AVR function

■ Overload and short-circuit protection

■ Battery reverse polarity protection (Optional)

■ Deep discharge protection

■ Cold start function

MODEL EP20-0624 PRO EP20-0824 PRO EP20-1024 PRO
Default Battery System Voltage 24VDC
INVERTER OUTPUT
Rated Power 600W 800W 1000W
Surge Rating 1800VA 2400VA 3000VA
Waveform Pure sine wave
Voltage Regulation Battery mode: 220 or 230VAC    Line mode: 220~240VAC
Output Frequency 50Hz / 60Hz
Invertert Frequency (Peak) >81%
Bypass Efficiency >95%
Output Transfer Time Typical:8ms 12ms(max)
AC INPUT
Voltage 220 / 230 / 240VAC
Selectable Voltage Range 140~280VAC ±5%
Low Battery Alarm 140VAC ±5%
Low Voltage Recover 150VAC ±5%
High Battery Alarm 280VAC ±5%
High Voltage Recover 270VAC ±5%
Low Frequency Alarm 45 ±5Hz
Low Frequency Recover 46 ±5Hz
High Frequency Alarm 65 ±5Hz
High Frequncy Recover 64 ±5Hz
Nominal Input Range 50Hz / 60Hz ±5Hz
AC Auto Restart YES
BATTERY
Minimum Start Voltage Low Battery Voltage Cutoff+0.5V
Low Battery Alarm Low Battery Voltage Cutoff+1.0V
Min battery voltage for power on Shutdown voltage +1V
Low Battery Cutoff 20.0-24.0VDC
High Battery Alarm (13.8-14.5V)+1V for 12VDC mode  (*2 for 24VDC)
AC CHARGE
Floating Voltage 27-29VDC
Boost Voltage 27.6~29VDC
Maximum Charge Current 600W 800W 1000W
10A 15A 15A
BYPASS & PROTECTION
Input Waveform Pure sine wave
Input Frequency 50Hz or 60Hz
Overload Protection >110%~125% Load foult affter 60s; >125%~150% Load foult affter 3s; >150% Load fault after 500ms
Over Temperature Protection ≥90℃
Bypass Output Protection 10A 250VAC
Output Circuit Protection YES
Battery Reverse Protection Optional
Battery Low Voltage Protection YES
Battery High Voltage Protection YES
Bypass Breaker Rating 10A
Maximum Bypass Current 10A
MECHANICAL SPECIFICATION
Machine Dimension (W*H*D) 319*300.5*132.2mm
Package Dimension (W*H*D) 391*325*187mm
Operating Temperature 0℃ ~40℃ 0~90% relative humidity (non-condensing)
Storage Temperature -15℃ to 55℃
Altitude ≤1000M
Audible Noise ≤60dB
Display LED+LCD
Cooling Mode Fan cooling
Fan Starting >45℃ starting, <30℃ Closing
Communication USB
CERTIFICATION & STANDARDS
CE-LVD (EN IEC62109-1:2010,EN IEC62109-2:2011)

CE-EMC+LVD (EN6100-6-4:2007, EN6100-6-2:2005+EN IEC62109-1:2010, EN IEC62109-2:2011) IEC60950-1:2005A+1:2009+A2:2013

EN IEC62040-1:2019

Headquarters